Solid State Relays
About Opto 22 Solid State Relays
In 1974, Opto22 introduced the first liquid epoxy-filled line of power solid-state relays (SSR). This innovation in SSR design greatly improved the reliability and reduced the cost of manufacturing. At that time, they also incorporated 100% testing under full-load conditions of every relay they manufactured.
Opto22 offers a complete line of SSRs, from the rugged 120/240/380-volt AC Series to the small footprint MP Series, designed for mounting on printed circuit boards. All Opto22 SSRs feature 4,000 volts of optical isolation. All are UL recognized, and most are CSA certified. The innovative use of room-temperature liquid epoxy encapsulation, coupled with Opto22’s unique heat-spreader technology, are key to mass producing the world’s most reliable solid-state relays.
View all Solid State Relays from Opto 22
P-Series Solid State Relays
P240D4
The P240D4 is a DC-controlled P Series relay that switches 240 VAC at up to 4 A.
P Model, 240 VAC, 4 Amp, DC Control Solid State Relay (SSR)
P240D4
Nominal AC Line Voltage | 240 |
Nominal Current Rating (Amps) | 4* |
1 cycle Surge (Amps) Peak | 85 |
Nominal Signal Input Resistance (Ohms) | 1000 |
Signal Pick-up Voltage | 3VDC** (24V allowed) |
Signal Drop-out Voltage | 1 VDC |
Peak Repetitive Voltage Maximum | 600 |
Maximum Output Voltage Drop | 1.6 volts |
Off-State Leakage mA Maximum*** | 5 mA |
Operating Voltage Range (Volts AC) | 24–280 |
I2t Rating t=8.3 (ms) | 30 |
Isolation Voltage | 4,000 VRMS |
θjc**** °C/Watt | 6.5 |
Dissipation Watts/Amp | 1.2 |
Agency Approvals | UL, CSA, RoHS, CE; UKCA |
Notes: * Ambient temperature will affect the current rating. For details, see the Thermal Ratings charts in the Solid State Relays Data Sheet (form 0859). ** = P Series 32 volts maximum. *** Operating Frequency: 25 to 65 Hz (operates at 400 Hz with 6 times the offstate leakage). ****θjc = Thermal resistance from internal junction to base. Maximum internal junction temperature is 110 °C. |
P120D4
The P120D4 is a DC-controlled P Series relay that switches 120 VAC at up to 4 A.
P Model, 120 VAC, 4 Amp, DC Control Solid State Relay (SSR)
P120D4
Nominal AC Line Voltage | 120 |
Nominal Current Rating (Amps) | 4* |
1 cycle Surge (Amps) Peak | 85 |
Nominal Signal Input Resistance (Ohms) | 1000 |
Signal Pick-up Voltage | 3VDC** (24V allowed) |
Signal Drop-out Voltage | 1 VDC |
Peak Repetitive Voltage Maximum | 600 |
Maximum Output Voltage Drop | 1.6 volts |
Off-State Leakage mA Maximum*** | 5 mA |
Operating Voltage Range (Volts AC) | 12–140 |
I2t Rating t=8.3 (ms) | 30 |
Isolation Voltage | 4,000 VRMS |
θjc**** °C/Watt | 6.5 |
Dissipation Watts/Amp | 1.2 |
Agency Approvals | UL, CSA, RoHS, CE; UKCA |
Notes: * Ambient temperature will affect the current rating. For details, see the Thermal Ratings charts in the Solid State Relays Data Sheet (form 0859). ** = P Series 32 volts maximum. *** Operating Frequency: 25 to 65 Hz (operates at 400 Hz with 6 times the offstate leakage). ****θjc = Thermal resistance from internal junction to base. Maximum internal junction temperature is 110 °C. |
DC60P
The DC60P is a DC-controlled P Series relay that switches 60 VDC at up to 3 A.
P Model, 60 VDC, 3 Amp, DC Control Solid State Relay (SSR)
DC60P
Operating Voltage Range | 5–60 VDC |
Forward Voltage Drop | 1.5 volts at 3 amps |
Nominal Current Rating (Amps) | 3* |
Off-State Blocking | 60 VDC |
Signal Pickup Voltage | 3 VDC 32 Volts** allowed |
Signal Dropout Voltage | 1 VDC |
Signal Input Impedance | 1,000 ohms |
1 Second Surge | 5 amps |
Operating Temp. Range | –40 °C to 100 °C |
Isolation Voltage | 4,000 VRMS |
Off-State Leakage | 1 mA maximum |
Package Type | P/MP series |
Turn-on Time | 100 microseconds |
Turn-off Time | 750 microseconds |
Agency Approvals | UL, CE, CSA, RoHS; UKCA |
Notes: * Ambient temperature will affect the current rating. For details, see the Thermal Ratings charts in the Solid State Relays Data Sheet (form 0859). ** MP series maximum allowed control signal is 24 VDC. |
DC200P
The DC200P is a DC-controlled P Series relay that switches 200 VDC at up to 1 A.
P Model, 200 VDC, 1 Amp, DC Control Solid State Relay (SSR)
DC200P
Operating Voltage Range | 5–200 VDC |
Forward Voltage Drop | 1.5 volts at 1 amp |
Nominal Current Rating (Amps) | 1* |
Off-State Blocking | 250 VDC |
Signal Pickup Voltage | 3 VDC 32 Volts** allowed |
Signal Dropout Voltage | 1 VDC |
Signal Input Impedance | 1,000 ohms |
1 Second Surge | 2 amps |
Operating Temp. Range | –40 °C to 100 °C |
Isolation Voltage | 4,000 VRMS |
Off-State Leakage | 1 mA maximum |
Package Type | P/MP series |
Turn-on Time | 100 microseconds |
Turn-off Time | 750 microseconds |
Agency Approvals | UL, CE, CSA, RoHS; UKCA |
Notes: * Ambient temperature will affect the current rating. For details, see the Thermal Ratings charts in the Solid State Relays Data Sheet (form 0859). ** MP series maximum allowed control signal is 24 VDC. |
MP-Series Solid State Relays
MP380D4
The MP380D4 is a DC-controlled MP Series relay that switches 380 VAC at up to 4 A.
MP Model, 380 VAC, 4 Amp, DC Control Solid State Relay (SSR)
MP380D4
Nominal AC Line Voltage | 380 |
Nominal Current Rating (Amps) | 4* |
1 cycle Surge (Amps) Peak | 85 |
Nominal Signal Input Resistance (Ohms) | 1000 |
Signal Pick-up Voltage | 3VDC** (24V allowed) |
Signal Drop-out Voltage | 1 VDC |
Peak Repetitive Voltage Maximum | 800 |
Maximum Output Voltage Drop | 1.6 volts |
Off-State Leakage mA Maximum*** | 5 mA |
Operating Voltage Range (Volts AC) | 24–420 |
I2t Rating t=8.3 (ms) | 30 |
Isolation Voltage | 4,000 VRMS |
θjc**** °C/Watt | 6.5 |
Dissipation Watts/Amp | 1.2 |
Agency Approvals | 2.5 FLA at 380 VAC 15 LRA at 380 VAC |
Notes: * Ambient temperature will affect the current rating. For details, see the Thermal Ratings charts in the Solid State Relays Data Sheet (form 0859). ** = P Series 32 volts maximum. *** Operating Frequency: 25 to 65 Hz (operates at 400 Hz with 6 times the offstate leakage). ****θjc = Thermal resistance from internal junction to base. Maximum internal junction temperature is 110 °C. |
MP240D4-17
This MP model, 240 VAC, 4 Amp, DC Control Solid State Relay (SSR) should be used as a replacement part only.
MP Model, 240 VAC, 4 Amp, DC Control Solid State Relay (SSR), Replacement Part Only
MP240D4 & MP240D4-17
Nominal AC Line Voltage | 240 |
Nominal Current Rating (Amps) | 4* |
1 cycle Surge (Amps) Peak | 85 |
Nominal Signal Input Resistance (Ohms) | 1000 |
Signal Pick-up Voltage | 3VDC** (24V allowed) |
Signal Drop-out Voltage | 1 VDC |
Peak Repetitive Voltage Maximum | 600 |
Maximum Output Voltage Drop | 1.6 volts |
Off-State Leakage mA Maximum*** | 5 mA |
Operating Voltage Range (Volts AC) | 24–280 |
I2t Rating t=8.3 (ms) | 30 |
Isolation Voltage | 4,000 VRMS |
θjc**** °C/Watt | 6.5 |
Dissipation Watts/Amp | 1.2 |
Rating (Motor Load) | 2.5 FLA at 240 VAC 15 LRA at 240 VAC |
Agency Approvals | UL, CSA, RoHS, CE; UKCA |
Notes: * Ambient temperature will affect the current rating. For details, see the Thermal Ratings charts in the Solid State Relays Data Sheet (form 0859). ** = P Series 32 volts maximum. *** Operating Frequency: 25 to 65 Hz (operates at 400 Hz with 6 times the offstate leakage). ****θjc = Thermal resistance from internal junction to base. Maximum internal junction temperature is 110 °C. |
MP240D4
The MP240D4 is a DC-controlled MP Series relay that switches 240 VAC at up to 4 A.
MP Model, 240 VAC, 4 Amp, DC Control Solid State Relay (SSR)
MP240D4 & MP240D4-17
Nominal AC Line Voltage | 240 |
Nominal Current Rating (Amps) | 4* |
1 cycle Surge (Amps) Peak | 85 |
Nominal Signal Input Resistance (Ohms) | 1000 |
Signal Pick-up Voltage | 3VDC** (24V allowed) |
Signal Drop-out Voltage | 1 VDC |
Peak Repetitive Voltage Maximum | 600 |
Maximum Output Voltage Drop | 1.6 volts |
Off-State Leakage mA Maximum*** | 5 mA |
Operating Voltage Range (Volts AC) | 24–280 |
I2t Rating t=8.3 (ms) | 30 |
Isolation Voltage | 4,000 VRMS |
θjc**** °C/Watt | 6.5 |
Dissipation Watts/Amp | 1.2 |
Rating (Motor Load) | 2.5 FLA at 240 VAC 15 LRA at 240 VAC |
Agency Approvals | UL, CSA, RoHS, CE; UKCA |
Notes: * Ambient temperature will affect the current rating. For details, see the Thermal Ratings charts in the Solid State Relays Data Sheet (form 0859). ** = P Series 32 volts maximum. *** Operating Frequency: 25 to 65 Hz (operates at 400 Hz with 6 times the offstate leakage). ****θjc = Thermal resistance from internal junction to base. Maximum internal junction temperature is 110 °C. |
MP240D2
The MP240D2 is a DC-controlled MP Series relay that switches 240 VAC at up to 2 A.
MP Model, 240 VAC, 2 Amp, DC Control Solid State Relay (SSR)
MP240D2
Nominal AC Line Voltage | 240 |
Nominal Current Rating (Amps) | 2* |
1 cycle Surge (Amps) Peak | 20 |
Nominal Signal Input Resistance (Ohms) | 1000 |
Signal Pick-up Voltage | 3VDC** (24V allowed) |
Signal Drop-out Voltage | 1 VDC |
Peak Repetitive Voltage Maximum | 600 |
Maximum Output Voltage Drop | 1.6 volts |
Off-State Leakage mA Maximum*** | 5 mA |
Operating Voltage Range (Volts AC) | 24–280 |
I2t Rating t=8.3 (ms) | 2 |
Isolation Voltage | 4,000 VRMS |
θjc**** °C/Watt | 20 |
Dissipation Watts/Amp | 1.2 |
Rating (Motor Load) | 1 FLA at 120 VAC 15 LRA at 120 VAC |
Agency Approvals | UL, CSA, RoHS, CE; UKCA |
Notes: * Ambient temperature will affect the current rating. For details, see the Thermal Ratings charts in the Solid State Relays Data Sheet (form 0859). ** = P Series 32 volts maximum. *** Operating Frequency: 25 to 65 Hz (operates at 400 Hz with 6 times the offstate leakage). ****θjc = Thermal resistance from internal junction to base. Maximum internal junction temperature is 110 °C. |
MP140D4
The MP120D4 is a DC-controlled MP Series relay that switches 120 VAC at up to 4 A.
MP Model, 120 VAC, 4 Amp, DC Control Solid State Relay (SSR)
MP140D4
Nominal AC Line Voltage | 120 |
Nominal Current Rating (Amps) | 4* |
1 cycle Surge (Amps) Peak | 85 |
Nominal Signal Input Resistance (Ohms) | 1000 |
Signal Pick-up Voltage | 3VDC** (24V allowed) |
Signal Drop-out Voltage | 1 VDC |
Peak Repetitive Voltage Maximum | 600 |
Maximum Output Voltage Drop | 1.6 volts |
Off-State Leakage mA Maximum*** | 5 mA |
Operating Voltage Range (Volts AC) | 12–140 |
I2t Rating t=8.3 (ms) | 30 |
Isolation Voltage | 4,000 VRMS |
θjc**** °C/Watt | 6.5 |
Dissipation Watts/Amp | 1.2 |
Rating (Motor Load) | 2.5 FLA at 240 VAC 6 LRA at 240 VAC |
Agency Approvals | UL, CSA, RoHS, CE; UKCA |
Notes: * Ambient temperature will affect the current rating. For details, see the Thermal Ratings charts in the Solid State Relays Data Sheet (form 0859). ** = P Series 32 volts maximum. *** Operating Frequency: 25 to 65 Hz (operates at 400 Hz with 6 times the offstate leakage). ****θjc = Thermal resistance from internal junction to base. Maximum internal junction temperature is 110 °C. |
MP120D2
The MP120D2 is a DC-controlled MP Series relay that switches 120 VAC at up to 2 A.
MP Model, 120 VAC, 2 Amp, DC Control Solid State Relay (SSR)
MP120D2
Nominal AC Line Voltage | 120 |
Nominal Current Rating (Amps) | 2* |
1 cycle Surge (Amps) Peak | 20 |
Nominal Signal Input Resistance (Ohms) | 1000 |
Signal Pick-up Voltage | 3VDC** (24V allowed) |
Signal Drop-out Voltage | 1 VDC |
Peak Repetitive Voltage Maximum | 600 |
Maximum Output Voltage Drop | 1.6 volts |
Off-State Leakage mA Maximum*** | 5 mA |
Operating Voltage Range (Volts AC) | 12–140 |
I2t Rating t=8.3 (ms) | 2 |
Isolation Voltage | 4,000 VRMS |
θjc**** °C/Watt | 20 |
Dissipation Watts/Amp | 1.2 |
Rating (Motor Load) | 1 FLA at 120 VAC 6 LRA at 120 VAC |
Agency Approvals | UL, CSA, RoHS, CE; UKCA |
Notes: * Ambient temperature will affect the current rating. For details, see the Thermal Ratings charts in the Solid State Relays Data Sheet (form 0859). ** = P Series 32 volts maximum. *** Operating Frequency: 25 to 65 Hz (operates at 400 Hz with 6 times the offstate leakage). ****θjc = Thermal resistance from internal junction to base. Maximum internal junction temperature is 110 °C. |
DC60MP
The DC60MP is a DC-controlled MP Series relay that switches 60 VDC at up to 3 A.
MP Model, 60 VDC, 3 Amp, DC Control Solid State Relay (SSR)
DC60MP
Operating Voltage Range | 5–60 VDC |
Forward Voltage Drop | 1.5 volts at 3 amps |
Nominal Current Rating (Amps) | 3* |
Off-State Blocking | 60 VDC |
Signal Pickup Voltage | 3 VDC 32 Volts** allowed |
Signal Dropout Voltage | 1 VDC |
Signal Input Impedance | 1,000 ohms |
1 Second Surge | 5 amps |
Operating Temp. Range | –40 °C to 100 °C |
Isolation Voltage | 4,000 VRMS |
Off-State Leakage | 1 mA maximum |
Package Type | P/MP series |
Turn-on Time | 100 microseconds |
Turn-off Time | 750 microseconds |
Agency Approvals | UL, CE, CSA, RoHS; UKCA |
Notes: * Ambient temperature will affect the current rating. For details, see the Thermal Ratings charts in the Solid State Relays Data Sheet (form 0859). ** MP series maximum allowed control signal is 24 VDC. |
DC200MP
The DC200MP is a DC-controlled MP Series relay that switches 200 VDC at up to 1 A.
MP Model, 200 VDC, 1 Amp, DC Control Solid State Relay (SSR)
DC200MP
Operating Voltage Range | 5–200 VDC |
Forward Voltage Drop | 1.5 volts at 1 amp |
Nominal Current Rating (Amps) | 1* |
Off-State Blocking | 250 VDC |
Signal Pickup Voltage | 3 VDC 32 Volts** allowed |
Signal Dropout Voltage | 1 VDC |
Signal Input Impedance | 1,000 ohms |
1 Second Surge | 2 amps |
Operating Temp. Range | –40 °C to 100 °C |
Isolation Voltage | 4,000 VRMS |
Off-State Leakage | 1 mA maximum |
Package Type | P/MP series |
Turn-on Time | 100 microseconds |
Turn-off Time | 750 microseconds |
Agency Approvals | UL, CE, CSA, RoHS; UKCA |
Notes: * Ambient temperature will affect the current rating. For details, see the Thermal Ratings charts in the Solid State Relays Data Sheet (form 0859). ** MP series maximum allowed control signal is 24 VDC. |
Power Series AC Control Solid State Relays
240A45
The 240A45 is an AC-controlled Power Series relay that switches 240 VAC at up to 45 A.
240 VAC, 45 Amp, AC Control Solid State Relay (SSR)
240A45
Nominal AC Line Voltage | 240 |
Nominal Current Rating (Amps) | 45* |
1 cycle Surge (Amps) Peak | 650 |
Nominal Signal Input Resistance (Ohms) | 33K |
Signal Pick-up Voltage | 85 VAC (280 allowed) |
Signal Drop-out Voltage | 10 VAC |
Peak Repetitive Voltage Maximum | 600 |
Maximum Output Voltage Drop | 1.6 volts |
Off-State Leakage (mA) Maximum | 14 mA |
Operating Voltage Range (Volts AC) | 24–280 |
I2t Rating t=8.3 (ms) | 1750 |
Isolation Voltage | 4,000VRMS |
θjc** (°C/Watt) | 0.67 |
Dissipation (Watts/Amp) | 0.9 |
Notes: * Ambient temperature will affect the current rating. For details, see the Thermal Ratings charts in the Solid State Relays Data Sheet (form 0859). ** θjc = Thermal resistance from internal junction to base. Maximum internal junction temperature is 110 °C. |
240A25
The 240A25 is an AC-controlled Power Series relay that switches 240 VAC at up to 25 A.
240 VAC, 25 Amp, AC Control Solid State Relay (SSR)
240A25
Nominal AC Line Voltage | 240 |
Nominal Current Rating (Amps) | 25* |
1 cycle Surge (Amps) Peak | 250 |
Nominal Signal Input Resistance (Ohms) | 33K |
Signal Pick-up Voltage | 85 VAC (280 allowed) |
Signal Drop-out Voltage | 10 VAC |
Peak Repetitive Voltage Maximum | 600 |
Maximum Output Voltage Drop | 1.6 volts |
Off-State Leakage (mA) Maximum | 14 mA |
Operating Voltage Range (Volts AC) | 24–280 |
I2t Rating t=8.3 (ms) | 250 |
Isolation Voltage | 4,000VRMS |
θjc** (°C/Watt) | 1.2 |
Dissipation (Watts/Amp) | 1.3 |
Notes: * Ambient temperature will affect the current rating. For details, see the Thermal Ratings charts in the Solid State Relays Data Sheet (form 0859). ** θjc = Thermal resistance from internal junction to base. Maximum internal junction temperature is 110 °C. |
240A10
The 240A10 is an AC-controlled Power Series relay that switches 240 VAC at up to 10 A.
240 VAC, 10 Amp, AC Control Solid State Relay (SSR)
240A10
Nominal AC Line Voltage | 240 |
Nominal Current Rating (Amps) | 10* |
1 cycle Surge (Amps) Peak | 110 |
Nominal Signal Input Resistance (Ohms) | 33K |
Signal Pick-up Voltage | 85 VAC (280 allowed) |
Signal Drop-out Voltage | 10 VAC |
Peak Repetitive Voltage Maximum | 600 |
Maximum Output Voltage Drop | 1.6 volts |
Off-State Leakage (mA) Maximum | 14 mA |
Operating Voltage Range (Volts AC) | 24–280 |
I2t Rating t=8.3 (ms) | 50 |
Isolation Voltage | 4,000VRMS |
θjc** (°C/Watt) | 1.3 |
Dissipation (Watts/Amp) | 1.6 |
Notes: * Ambient temperature will affect the current rating. For details, see the Thermal Ratings charts in the Solid State Relays Data Sheet (form 0859). ** θjc = Thermal resistance from internal junction to base. Maximum internal junction temperature is 110 °C. |
120A25
The 120A25 is an AC-controlled Power Series relay that switches 120 VAC at up to 25 A.
120 VAC, 25 Amp, AC Control Solid State Relay (SSR)
120A25
Nominal AC Line Voltage | 120 |
Nominal Current Rating (Amps) | 25* |
1 cycle Surge (Amps) Peak | 250 |
Nominal Signal Input Resistance (Ohms) | 33K |
Signal Pick-up Voltage | 85 VAC (280 allowed) |
Signal Drop-out Voltage | 10 VAC |
Peak Repetitive Voltage Maximum | 600 |
Maximum Output Voltage Drop | 1.6 volts |
Off-State Leakage (mA) Maximum | 7 mA |
Operating Voltage Range (Volts AC) | 12–140 |
I2t Rating t=8.3 (ms) | 250 |
Isolation Voltage | 4,000VRMS |
θjc** (°C/Watt) | 1.2 |
Dissipation (Watts/Amp) | 1.3 |
Notes: * Ambient temperature will affect the current rating. For details, see the Thermal Ratings charts in the Solid State Relays Data Sheet (form 0859). ** θjc = Thermal resistance from internal junction to base. Maximum internal junction temperature is 110 °C. |
120A10
The 120A10 is an AC-controlled Power Series relay that switches 120 VAC at up to 10 A.
120 VAC, 10 Amp, AC Control Solid State Relay (SSR)
120A10
Nominal AC Line Voltage | 120 |
Nominal Current Rating (Amps) | 10* |
1 cycle Surge (Amps) Peak | 110 |
Nominal Signal Input Resistance (Ohms) | 33K |
Signal Pick-up Voltage | 85 VAC (280 allowed) |
Signal Drop-out Voltage | 10 VAC |
Peak Repetitive Voltage Maximum | 600 |
Maximum Output Voltage Drop | 1.6 volts |
Off-State Leakage (mA) Maximum | 7 mA |
Operating Voltage Range (Volts AC) | 12–140 |
I2t Rating t=8.3 (ms) | 50 |
Isolation Voltage | 4,000VRMS |
θjc** (°C/Watt) | 1.3 |
Dissipation (Watts/Amp) | 1.6 |
Notes: * Ambient temperature will affect the current rating. For details, see the Thermal Ratings charts in the Solid State Relays Data Sheet (form 0859). ** θjc = Thermal resistance from internal junction to base. Maximum internal junction temperature is 110 °C. |
Power Series DC Control Solid State Relays
240Di10
The 240Di10 is a DC-controlled Power Series relay that switches 240 VAC at up to 10 A. It includes a built-in LED to indicate operation.
240 VAC, 10 Amp, DC Control Solid State Relay (SSR), with LED Indicator
240Di10
Nominal AC Line Voltage | 240 |
Nominal Current Rating (Amps) | 10* |
1 cycle Surge (Amps) Peak | 110 |
Nominal Signal Input Resistance (Ohms) | 730 |
Signal Pick-up Voltage | 3VDC (32V allowed) |
Signal Drop-out Voltage | 1 VDC |
Peak Repetitive Voltage Maximum | 600 |
Maximum Output Voltage Drop | 1.6 volts |
Off-State Leakage (mA) Maximum | 14 mA |
Operating Voltage Range (Volts AC) | 24–280 |
I2t Rating t=8.3 (ms) | 50 |
Isolation Voltage | 4,000VRMS |
θjc** (°C/Watt) | 1.3 |
Dissipation (Watts/Amp) | 1.6 |
Notes: * Ambient temperature will affect the current rating. For details, see the Thermal Ratings charts in the Solid State Relays Data Sheet (form 0859). ** θjc = Thermal resistance from internal junction to base. Maximum internal junction temperature is 110 °C. |
240Di25
The 240Di25 is a DC-controlled Power Series relay that switches 240 VAC at up to 25 A. It includes a built-in LED to indicate operation.
240 VAC, 25 Amp, DC Control Solid State Relay (SSR) with LED Indicator
240Di25
Nominal AC Line Voltage | 240 |
Nominal Current Rating (Amps) | 25* |
1 cycle Surge (Amps) Peak | 250 |
Nominal Signal Input Resistance (Ohms) | 730 |
Signal Pick-up Voltage | 3VDC (32V allowed) |
Signal Drop-out Voltage | 1 VDC |
Peak Repetitive Voltage Maximum | 600 |
Maximum Output Voltage Drop | 1.6 volts |
Off-State Leakage (mA) Maximum | 14 mA |
Operating Voltage Range (Volts AC) | 12–280 |
I2t Rating t=8.3 (ms) | 250 |
Isolation Voltage | 4,000VRMS |
θjc** (°C/Watt) | 1.2 |
Dissipation (Watts/Amp) | 1.3 |
Notes: * Ambient temperature will affect the current rating. For details, see the Thermal Ratings charts in the Solid State Relays Data Sheet (form 0859). ** θjc = Thermal resistance from internal junction to base. Maximum internal junction temperature is 110 °C. |
240Di45
The 240Di45 is a DC-controlled Power Series relay that switches 240 VAC at up to 45 A. It includes a built-in LED to indicate operation.
240 VAC, 45 Amp, DC Control Solid State Relay (SSR) with LED Indicator
240Di45
Nominal AC Line Voltage | 240 |
Nominal Current Rating (Amps) | 45* |
1 cycle Surge (Amps) Peak | 650 |
Nominal Signal Input Resistance (Ohms) | 730 |
Signal Pick-up Voltage | 3VDC (32V allowed) |
Signal Drop-out Voltage | 1 VDC |
Peak Repetitive Voltage Maximum | 600 |
Maximum Output Voltage Drop | 1.6 volts |
Off-State Leakage (mA) Maximum | 14 mA |
Operating Voltage Range (Volts AC) | 24–280 |
I2t Rating t=8.3 (ms) | 1750 |
Isolation Voltage | 4,000VRMS |
θjc** (°C/Watt) | 0.67 |
Dissipation (Watts/Amp) | 0.9 |
Notes: * Ambient temperature will affect the current rating. For details, see the Thermal Ratings charts in the Solid State Relays Data Sheet (form 0859). ** θjc = Thermal resistance from internal junction to base. Maximum internal junction temperature is 110 °C. |
575Di45-12
The 575Di45-12 is a DC-controlled Power Series relay that switches 575 VAC at up to 45 A. This SSR is transient proof and includes a built-in LED to indicate operation.
575 VAC, 45 Amp, DC Control Solid State Relay (SSR) with LED Indicator, Transient Proof
575Di45-12
Nominal AC Line Voltage | 575 |
Nominal Current Rating (Amps) | 45* |
1 cycle Surge (Amps) Peak | 650 |
Nominal Signal Input Resistance (Ohms) | 730 |
Signal Pick-up Voltage | 3VDC (32V allowed) |
Signal Drop-out Voltage | 1 VDC |
Peak Repetitive Voltage Maximum | 1000 |
Maximum Output Voltage Drop | 1.6 volts |
Off-State Leakage (mA) Maximum | 15 mA |
Operating Voltage Range (Volts AC) | 100–600 |
I2t Rating t=8.3 (ms) | 1750 |
Isolation Voltage | 4,000VRMS |
θjc** (°C/Watt) | 0.67 |
Dissipation (Watts/Amp) | 0.9 |
Agency Approvals | UL, CE, RoHS; UKCA |
Notes: * Ambient temperature will affect the current rating. For details, see the Thermal Ratings charts in the Solid State Relays Data Sheet (form 0859). ** Operating Frequency: 25 to 65 Hz (operates at 400 Hz with 6 times the offstate leakage). ***θjc = Thermal resistance from internal junction to base. Maximum internal junction temperature is 110 °C. |
575D45-12
The 575D45-12 is a DC-controlled Power Series relay that switches 575 VAC at up to 45 A. This SSR is transient proof.
575 VAC, 45 Amp, DC Control Solid State Relay (SSR), Transient Proof
575D45-12
Nominal AC Line Voltage | 575 |
Nominal Current Rating (Amps) | 45* |
1 cycle Surge (Amps) Peak | 650 |
Nominal Signal Input Resistance (Ohms) | 1000 |
Signal Pick-up Voltage | 3VDC (32V allowed) |
Signal Drop-out Voltage | 1 VDC |
Peak Repetitive Voltage Maximum | 1000 |
Maximum Output Voltage Drop | 1.6 volts |
Off-State Leakage (mA) Maximum | 15 mA |
Operating Voltage Range (Volts AC) | 100–600 |
I2t Rating t=8.3 (ms) | 1750 |
Isolation Voltage | 4,000VRMS |
θjc** (°C/Watt) | 0.67 |
Dissipation (Watts/Amp) | 0.9 |
Agency Approvals | UL, CE, CSA, RoHS; UKCA |
Notes: * Ambient temperature will affect the current rating. For details, see the Thermal Ratings charts in the Solid State Relays Data Sheet (form 0859). ** Operating Frequency: 25 to 65 Hz (operates at 400 Hz with 6 times the offstate leakage). ***θjc = Thermal resistance from internal junction to base. Maximum internal junction temperature is 110 °C. |
575D15-12
The 575D15-12 is a DC-controlled Power Series relay that switches 575 VAC at up to 15 A. This SSR is transient proof.
575 VAC, 15 Amp, DC Control Solid State Relay (SSR), Transient Proof
575D15-12
Nominal AC Line Voltage | 575 |
Nominal Current Rating (Amps) | 15* |
1 cycle Surge (Amps) Peak | 150 |
Nominal Signal Input Resistance (Ohms) | 1000 |
Signal Pick-up Voltage | 3VDC (32V allowed) |
Signal Drop-out Voltage | 1 VDC |
Peak Repetitive Voltage Maximum | 1200 |
Maximum Output Voltage Drop | 3.2 volts |
Off-State Leakage (mA) Maximum | 15 mA |
Operating Voltage Range (Volts AC) | 100–600 |
I2t Rating t=8.3 (ms) | 90 |
Isolation Voltage | 4,000VRMS |
θjc** (°C/Watt) | 1.2 |
Dissipation (Watts/Amp) | 2.5 |
Agency Approvals | CE, CSA, RoHS; UKCA |
Notes: * Ambient temperature will affect the current rating. For details, see the Thermal Ratings charts in the Solid State Relays Data Sheet (form 0859). ** Operating Frequency: 25 to 65 Hz (operates at 400 Hz with 6 times the offstate leakage). ***θjc = Thermal resistance from internal junction to base. Maximum internal junction temperature is 110 °C. |
480D45-12
The 480D45-12 is a DC-controlled Power Series relay that switches 480 VAC at up to 45 A. This SSR is transient proof.
480 VAC, 45 Amp, DC Control Solid State Relay (SSR), Transient Proof
480D45-12
Nominal AC Line Voltage | 480 |
Nominal Current Rating (Amps) | 25* |
1 cycle Surge (Amps) Peak | 650 |
Nominal Signal Input Resistance (Ohms) | 1000 |
Signal Pick-up Voltage | 3VDC (32V allowed) |
Signal Drop-out Voltage | 1 VDC |
Peak Repetitive Voltage Maximum | 1200 |
Maximum Output Voltage Drop | 3.2 volts |
Off-State Leakage (mA) Maximum | 11 mA |
Operating Voltage Range (Volts AC) | 100–530 |
I2t Rating t=8.3 (ms) | 1750 |
Isolation Voltage | 4,000VRMS |
θjc** (°C/Watt) | 0.67 |
Dissipation (Watts/Amp) | 0.9 |
Agency Approvals | UL, CE, CSA, RoHS; UKCA |
Notes: * Ambient temperature will affect the current rating. For details, see the Thermal Ratings charts in the Solid State Relays Data Sheet (form 0859). ** Operating Frequency: 25 to 65 Hz (operates at 400 Hz with 6 times the offstate leakage). ***θjc = Thermal resistance from internal junction to base. Maximum internal junction temperature is 110 °C. |
480D25-12
The 480D25-12 is a DC-controlled Power Series relay that switches 480 VAC at up to 25 A. This SSR is transient proof.
480 VAC, 25 Amp, DC Control Solid State Relay (SSR), Transient Proof
480D25-12
Nominal AC Line Voltage | 480 |
Nominal Current Rating (Amps) | 25* |
1 cycle Surge (Amps) Peak | 250 |
Nominal Signal Input Resistance (Ohms) | 1000 |
Signal Pick-up Voltage | 3VDC (32V allowed) |
Signal Drop-out Voltage | 1 VDC |
Peak Repetitive Voltage Maximum | 1200 |
Maximum Output Voltage Drop | 3.2 volts |
Off-State Leakage (mA) Maximum | 11 mA |
Operating Voltage Range (Volts AC) | 100–530 |
I2t Rating t=8.3 (ms) | 250 |
Isolation Voltage | 4,000VRMS |
θjc** (°C/Watt) | 1.3 |
Dissipation (Watts/Amp) | 1.3 |
Agency Approvals | UL, CE, CSA, RoHS; UKCA |
Notes: * Ambient temperature will affect the current rating. For details, see the Thermal Ratings charts in the Solid State Relays Data Sheet (form 0859). ** Operating Frequency: 25 to 65 Hz (operates at 400 Hz with 6 times the offstate leakage). ***θjc = Thermal resistance from internal junction to base. Maximum internal junction temperature is 110 °C. |
480D15-12
The 480D15-12 is a DC-controlled Power Series relay that switches 480 VAC at up to 15 A. This SSR is transient proof.
480 VAC, 15 Amp, DC Control Solid State Relay (SSR), Transient Proof
480D15-12
Nominal AC Line Voltage | 480 |
Nominal Current Rating (Amps) | 15* |
1 cycle Surge (Amps) Peak | 150 |
Nominal Signal Input Resistance (Ohms) | 1000 |
Signal Pick-up Voltage | 3 VDC (32V Allowed) |
Signal Drop-out Voltage | 1 VDC |
Peak Repetitive Voltage Maximum | 1200 |
Maximum Output Voltage Drop | 3.2 volts |
Off-State Leakage (mA) Maximum** | 11 mA |
Operating Voltage Range (Volts AC) | 100–530 |
I2t Ratingt=8.3 (ms) | 50 |
Isolation Voltage | 4,000VRMS |
θjc*** (°C/Watt) | 1.2 |
Dissipation (Watts/Amp) | 2.5 |
Agency Approvals | UL, CE, CSA, RoHS; UKCA |
Notes: * Ambient temperature will affect the current rating. For details, see the Thermal Ratings charts in the Solid State Relays Data Sheet (form 0859). ** Operating Frequency: 25 to 65 Hz (operates at 400 Hz with 6 times the offstate leakage). ***θjc = Thermal resistance from internal junction to base. Maximum internal junction temperature is 110 °C. |
480D10-12
The 480D10-12 is a DC-controlled Power Series relay that switches 480 VAC at up to 10 A. This SSR is transient proof.
480 VAC, 10 Amp, DC Control Solid State Relay (SSR), Transient Proof
480D10-12
Nominal AC Line Voltage | 480 |
Nominal Current Rating (Amps) | 10* |
1 cycle Surge (Amps) Peak | 110 |
Nominal Signal Input Resistance (Ohms) | 1000 |
Signal Pick-up Voltage | 3 VDC (32V Allowed) |
Signal Drop-out Voltage | 1 VDC |
Peak Repetitive Voltage Maximum | 1200 |
Maximum Output Voltage Drop | 3.2 volts |
Off-State Leakage (mA) Maximum** | 11 mA |
Operating Voltage Range (Volts AC) | 100–530 |
I2t Ratingt=8.3 (ms) | 50 |
Isolation Voltage | 4,000VRMS |
θjc*** (°C/Watt) | 1.2 |
Dissipation (Watts/Amp) | 2.5 |
Agency Approvals | UL, CE, CSA, RoHS; UKCA |
Notes: * Ambient temperature will affect the current rating. For details, see the Thermal Ratings charts in the Solid State Relays Data Sheet (form 0859). ** Operating Frequency: 25 to 65 Hz (operates at 400 Hz with 6 times the offstate leakage). ***θjc = Thermal resistance from internal junction to base. Maximum internal junction temperature is 110 °C. |
380D45
The 380D45 is a DC-controlled Power Series relay that switches 380 VAC at up to 45 A.
380 VAC, 45 Amp, DC Control Solid State Relay (SSR)
380D45
Nominal AC Line Voltage | 380 |
Nominal Current Rating (Amps) | 45* |
1 cycle Surge (Amps) Peak | 650 |
Nominal Signal Input Resistance (Ohms) | 1000 |
Signal Pick-up Voltage | 3 VDC (32V Allowed) |
Signal Drop-out Voltage | 1 VDC |
Peak Repetitive Voltage Maximum | 800 |
Maximum Output Voltage Drop | 3.2 volts |
Off-State Leakage (mA) Maximum** | 12 mA |
Operating Voltage Range (Volts AC) | 24–420 |
I2t Ratingt=8.3 (ms) | 1750 |
Isolation Voltage | 4,000VRMS |
θjc*** (°C/Watt) | 0.67 |
Dissipation (Watts/Amp) | 0.9 |
Notes: * Ambient temperature will affect the current rating. For details, see the Thermal Ratings charts in the Solid State Relays Data Sheet (form 0859). ** θjc = Thermal resistance from internal junction to base. Maximum internal junction temperature is 110 °C. |
380D25
The 380D25 is a DC-controlled Power Series relay that switches 380 VAC at up to 25 A.
380 VAC, 25 Amp, DC Control Solid State Relay (SSR)
380D25
Nominal AC Line Voltage | 380 |
Nominal Current Rating (Amps) | 25* |
1 cycle Surge (Amps) Peak | 250 |
Nominal Signal Input Resistance (Ohms) | 1000 |
Signal Pick-up Voltage | 3 VDC (32V Allowed) |
Signal Drop-out Voltage | 1 VDC |
Peak Repetitive Voltage Maximum | 800 |
Maximum Output Voltage Drop | 1.6 volts |
Off-State Leakage (mA) Maximum** | 12 mA |
Operating Voltage Range (Volts AC) | 24–420 |
I2t Ratingt=8.3 (ms) | 250 |
Isolation Voltage | 4,000VRMS |
θjc*** (°C/Watt) | 1.2 |
Dissipation (Watts/Amp) | 1.3 |
Notes: * Ambient temperature will affect the current rating. For details, see the Thermal Ratings charts in the Solid State Relays Data Sheet (form 0859). ** θjc = Thermal resistance from internal junction to base. Maximum internal junction temperature is 110 °C. |
240D45
The 240D45 is a DC-controlled Power Series relay that switches 240 VAC at up to 45 A.
240 VAC, 45 Amp, DC Control Solid State Relay (SSR)
240D45
Nominal AC Line Voltage | 240 |
Nominal Current Rating (Amps) | 45* |
1 cycle Surge (Amps) Peak | 650 |
Nominal Signal Input Resistance (Ohms) | 1000 |
Signal Pick-up Voltage | 3VDC (32V allowed) |
Signal Drop-out Voltage | 1 VDC |
Peak Repetitive Voltage Maximum | 600 |
Maximum Output Voltage Drop | 1.6 volts |
Off-State Leakage (mA) Maximum** | 14 mA |
Operating Voltage Range (Volts AC) | 24-280 |
I2t Ratingt=8.3 (ms) | 1750 |
Isolation Voltage | 4,000VRMS |
θjc*** (°C/Watt) | 0.67 |
Dissipation (Watts/Amp) | 0.9 |
Notes: θjc* = Thermal resistance junction to base. Maximum junction temperature is 110 °C. |
240D3
The 240D3 is a DC-controlled Power Series relay that switches 240 VAC at up to 3 A.
240 VAC, 3 Amp, DC Control Solid State Relay (SSR)
240D3
Nominal AC Line Voltage | 240 |
Nominal Current Rating (Amps) | 3* |
1 cycle Surge (Amps) Peak | 85 |
Nominal Signal Input Resistance (Ohms) | 1000 |
Signal Pick-up Voltage | 3VDC (32V allowed) |
Signal Drop-out Voltage | 1 VDC |
Peak Repetitive Voltage Maximum | 600 |
Maximum Output Voltage Drop | 1.6 volts |
Off-State Leakage (mA) Maximum** | 5 mA |
Operating Voltage Range (Volts AC) | 24-280 |
I2t Ratingt=8.3 (ms) | 30 |
Isolation Voltage | 4,000VRMS |
θjc*** (°C/Watt) | 11 |
Dissipation (Watts/Amp) | 1.7 |
Notes: θjc* = Thermal resistance junction to base. Maximum junction temperature is 110 °C. |
240D25-17
This 240 VAC, 25Amp, DC Control Solid State Relay (SSR) should be used as a replacement part only.
240 VAC, 25 Amp, DC Control Solid State Relay (SSR), Replacement Part Only
240D25-17
Nominal AC Line Voltage | 240 |
Nominal Current Rating (Amps) | 25 |
1 cycle Surge (Amps) Peak | 250 |
Nominal Signal Input Resistance (Ohms) | 1000 |
Signal Pick-up Voltage | 3VDC (32V allowed) |
Signal Drop-out Voltage | 1 VDC |
Peak Repetitive Voltage Maximum | 600 |
Maximum Output Voltage Drop | 1.6 volts |
Off-State Leakage (mA) Maximum** | 14 mA |
Operating Voltage Range (Volts AC) | 24-280 |
I2t Ratingt=8.3 (ms) | 250 |
Isolation Voltage | 4,000VRMS |
θjc*** (°C/Watt) | 1.2 |
Dissipation (Watts/Amp) | 1.3 |
Notes: θjc* = Thermal resistance junction to base. Maximum junction temperature is 110 °C. |
240D45-17
This 240 VAC, 45 Amp, DC Control Solid State Relay (SSR) should be used as a replacement part only.
380 VAC, 25 Amp, DC Control Solid State Relay (SSR)
240D45-17
Nominal AC Line Voltage | 240 |
Nominal Current Rating (Amps) | 45 |
1 cycle Surge (Amps) Peak | 650 |
Nominal Signal Input Resistance (Ohms) | 1000 |
Signal Pick-up Voltage | 3VDC (32V allowed) |
Signal Drop-out Voltage | 1 VDC |
Peak Repetitive Voltage Maximum | 600 |
Maximum Output Voltage Drop | 1.6 volts |
Off-State Leakage (mA) Maximum** | 14 mA |
Operating Voltage Range (Volts AC) | 24-280 |
I2t Ratingt=8.3 (ms) | 1750 |
Isolation Voltage | 4,000VRMS |
θjc*** (°C/Watt) | 0.67 |
Dissipation (Watts/Amp) | 0.9 |
Notes: θjc* = Thermal resistance junction to base. Maximum junction temperature is 110 °C. |
240D10-17
This 240 VAC, 10 Amp, DC Control Solid State Relay (SSR) should be used as a replacement part only.
240 VAC, 10 Amp, DC Control Solid State Relay (SSR), Replacement Part Only
240D25
Nominal AC Line Voltage | 240 |
Nominal Current Rating (Amps) | 25 |
1 cycle Surge (Amps) Peak | 250 |
Nominal Signal Input Resistance (Ohms) | 1000 |
Signal Pick-up Voltage | 3VDC (32V allowed) |
Signal Drop-out Voltage | 1 VDC |
Peak Repetitive Voltage Maximum | 600 |
Maximum Output Voltage Drop | 1.6 volts |
Off-State Leakage (mA) Maximum** | 14 mA |
Operating Voltage Range (Volts AC) | 24-280 |
I2t Ratingt=8.3 (ms) | 250 |
Isolation Voltage | 4,000VRMS |
θjc*** (°C/Watt) | 1.2 |
Dissipation (Watts/Amp) | 1.3 |
Notes: θjc* = Thermal resistance junction to base. Maximum junction temperature is 110 °C. |
240D10
The 240D10 is a DC-controlled Power Series relay that switches 240 VAC at up to 10 A.
240 VAC, 10 Amp, DC Control Solid State Relay (SSR)
240D10
Nominal AC Line Voltage | 240 |
Nominal Current Rating (Amps) | 10* |
1 cycle Surge (Amps) Peak | 110 |
Nominal Signal Input Resistance (Ohms) | 1000 |
Signal Pick-up Voltage | 3VDC (32V allowed) |
Signal Drop-out Voltage | 1 VDC |
Peak Repetitive Voltage Maximum | 600 |
Maximum Output Voltage Drop | 1.6 volts |
Off-State Leakage (mA) Maximum** | 14 mA |
Operating Voltage Range (Volts AC) | 24–280 |
I2t Ratingt=8.3 (ms) | 50 |
Isolation Voltage | 4,000VRMS |
θjc*** (°C/Watt) | 1.3 |
Dissipation (Watts/Amp) | 1.6 |
Notes: * Ambient temperature will affect the current rating. For details, see the Thermal Ratings charts in the Solid State Relays Data Sheet (form 0859). ** θjc = Thermal resistance from internal junction to base. Maximum internal junction temperature is 110 °C. |
120D45
The 120D45 is a DC-controlled Power Series relay that switches 120 VAC at up to 45 A.
120 VAC, 45 Amp, DC Control Solid State Relay (SSR)
120D45
Nominal AC Line Voltage | 120 |
Nominal Current Rating (Amps) | 45* |
1 cycle Surge (Amps) Peak | 650 |
Nominal Signal Input Resistance (Ohms) | 1000 |
Signal Pick-up Voltage | 3VDC (32V allowed) |
Signal Drop-out Voltage | 1 VDC |
Peak Repetitive Voltage Maximum | 600 |
Maximum Output Voltage Drop | 1.6 volts |
Off-State Leakage (mA) Maximum** | 7 mA |
Operating Voltage Range (Volts AC) | 12–140 |
I2t Ratingt=8.3 (ms) | 1750 |
Isolation Voltage | 4,000VRMS |
θjc*** (°C/Watt) | 0.67 |
Dissipation (Watts/Amp) | 0.9 |
Notes: * Ambient temperature will affect the current rating. For details, see the Thermal Ratings charts in the Solid State Relays Data Sheet (form 0859). ** θjc = Thermal resistance from internal junction to base. Maximum internal junction temperature is 110 °C. |
120D3
The 120D3 is a DC-controlled Power Series relay that switches 120 VAC at up to 3 A.
120 VAC, 3 Amp, DC Control Solid State Relay (SSR)
120D3
Nominal AC Line Voltage | 120 |
Nominal Current Rating (Amps) | 3* |
1 cycle Surge (Amps) Peak | 85 |
Nominal Signal Input Resistance (Ohms) | 1000 |
Signal Pick-up Voltage | 3VDC (32V allowed) |
Signal Drop-out Voltage | 1 VDC |
Peak Repetitive Voltage Maximum | 600 |
Maximum Output Voltage Drop | 1.6 volts |
Off-State Leakage (mA) Maximum** | 2.5mA |
Operating Voltage Range (Volts AC) | 12–140 |
I2t Ratingt=8.3 (ms) | 30 |
Isolation Voltage | 4,000VRMS |
θjc*** (°C/Watt) | 11 |
Dissipation (Watts/Amp) | 1.7 |
Notes: * Ambient temperature will affect the current rating. For details, see the Thermal Ratings charts in the Solid State Relays Data Sheet (form 0859). ** θjc = Thermal resistance from internal junction to base. Maximum internal junction temperature is 110 °C. |
120D25
The 120D25 is a DC-controlled Power Series relay that switches 120 VAC at up to 25 A.
120 VAC, 25 Amp, DC Control Solid State Relay (SSR)
120D25
Nominal AC Line Voltage | 120 |
Nominal Current Rating (Amps) | 25* |
1 cycle Surge (Amps) Peak | 250 |
Nominal Signal Input Resistance (Ohms) | 1000 |
Signal Pick-up Voltage | 3VDC (32V allowed) |
Signal Drop-out Voltage | 1 VDC |
Peak Repetitive Voltage Maximum | 600 |
Maximum Output Voltage Drop | 1.6 volts |
Off-State Leakage (mA) Maximum** | 7 mA |
Operating Voltage Range (Volts AC) | 12–140 |
I2t Ratingt=8.3 (ms) | 250 |
Isolation Voltage | 4,000VRMS |
θjc*** (°C/Watt) | 1.2 |
Dissipation (Watts/Amp) | 1.3 |
Notes: * Ambient temperature will affect the current rating. For details, see the Thermal Ratings charts in the Solid State Relays Data Sheet (form 0859). ** θjc = Thermal resistance from internal junction to base. Maximum internal junction temperature is 110 °C. |
120D10
The 120D10 is a DC-controlled Power Series relay that switches 120 VAC at up to 10 A.
120 VAC, 10 Amp, DC Control Solid State Relay (SSR)
120D10
Nominal AC Line Voltage | 120 |
Nominal Current Rating (Amps) | 10* |
1 cycle Surge (Amps) Peak | 110 |
Nominal Signal Input Resistance (Ohms) | 1000 |
Signal Pick-up Voltage | 3VDC (32V allowed) |
Signal Drop-out Voltage | 1 VDC |
Peak Repetitive Voltage Maximum | 600 |
Maximum Output Voltage Drop | 1.6 volts |
Off-State Leakage (mA) Maximum** | 7 mA |
Operating Voltage Range (Volts AC) | 12–140 |
I2t Ratingt=8.3 (ms) | 50 |
Isolation Voltage | 4,000VRMS |
θjc*** (°C/Watt) | 1.3 |
Dissipation (Watts/Amp) | 1.6 |
Notes: * Ambient temperature will affect the current rating. For details, see the Thermal Ratings charts in the Solid State Relays Data Sheet (form 0859). ** θjc = Thermal resistance from internal junction to base. Maximum internal junction temperature is 110 °C. |
DC60S5
The DC60S5 is a DC-controlled Power Series relay that switches 60 VDC at up to 5 A.
60 VDC, 5 Amp, DC Control Solid State Relay (SSR)
DC60S5
Operating Voltage Range | 5–60 VDC |
Forward Voltage Drop | 1.5 volts at 5 amps |
Nominal Current Rating (Amps) | 5* |
Off-State Blocking | 60 VDC |
Signal Pickup Voltage | 3 VDC 32 Volts allowed |
Signal Dropout Voltage | 1 VDC |
Signal Input Impedance | 1,000 ohms |
1 Second Surge | 10 amps |
Operating Temp. Range | –40 °C to 100 °C |
Isolation Voltage | 4,000 VRMS |
Off-State Leakage | 1 mA maximum |
Package Type | Power series |
Turn-on Time | 100 microseconds |
Turn-off Time | 750 microseconds |
Agency Approvals | UL, CE, CSA, RoHS; UKCA |
Notes: * Ambient temperature will affect the current rating. For details, see the Thermal Ratings charts in the Solid State Relays Data Sheet (form 0859). ** MP series maximum allowed control signal is 24 VDC. |
DC60S3
The DC60S3 is a DC-controlled Power Series relay that switches 60 VDC at up to 3 A.
60 VDC, 3 Amp, DC Control Solid State Relay (SSR)
DC60S3
Operating Voltage Range | 5–60 VDC |
Forward Voltage Drop | 1.5 volts at 5 amps |
Nominal Current Rating (Amps) | 3* |
Off-State Blocking | 60 VDC |
Signal Pickup Voltage | 3 VDC 32 Volts allowed |
Signal Dropout Voltage | 1 VDC |
Signal Input Impedance | 1,000 ohms |
1 Second Surge | 5 amps |
Operating Temp. Range | –40 °C to 100 °C |
Isolation Voltage | 4,000 VRMS |
Off-State Leakage | 1 mA maximum |
Package Type | Power series |
Turn-on Time | 100 microseconds |
Turn-off Time | 750 microseconds |
Agency Approvals | UL, CE, CSA, RoHS; UKCA |
Notes: * Ambient temperature will affect the current rating. For details, see the Thermal Ratings charts in the Solid State Relays Data Sheet (form 0859). ** MP series maximum allowed control signal is 24 VDC. |
240D25
The 240D25 is a DC-controlled Power Series relay that switches 240 VAC at up to 25 A.
240 VAC, 25 Amp, DC Control Solid State Relay (SSR)
240D25
Nominal AC Line Voltage | 240 |
Nominal Current Rating (Amps) | 25 |
1 cycle Surge (Amps) Peak | 250 |
Nominal Signal Input Resistance (Ohms) | 1000 |
Signal Pick-up Voltage | 3VDC (32V allowed) |
Signal Drop-out Voltage | 1 VDC |
Peak Repetitive Voltage Maximum | 600 |
Maximum Output Voltage Drop | 1.6 volts |
Off-State Leakage (mA) Maximum** | 14 mA |
Operating Voltage Range (Volts AC) | 24-280 |
I2t Ratingt=8.3 (ms) | 250 |
Isolation Voltage | 4,000VRMS |
θjc*** (°C/Watt) | 1.2 |
Dissipation (Watts/Amp) | 1.3 |
Notes: θjc* = Thermal resistance junction to base. Maximum junction temperature is 110 °C. |
Power Series Accessories Solid State Relays
SAFETY COVER
The Opto 22 solid state relay (SSR) safety cover for Opto 22 Power Series SSRs reduces the chance of accidental contact with relay terminals, while providing access holes for test instrumentation.
Solid State Relay (SSR) Cover for Power Series Standard Model
SSR-HS
Custom designed for the Power Series SSRs, the SSR-HS heatsink provides excellent heat dissipation when mounted to the SSR with a matching thermal conductive pad, which is used in place of silicon grease. One thermal pad is included with the heatsink. Also includes a DIN-rail adapter.
Solid State Relay (SSR) Heatsink for Power Series Standard Model
SSR-Thermopad
Used instead of silicon grease, this thermal conductive pad is custom designed for the Power Series SSR heatsink (SSR-HS). Pack of 10.
Thermal conductive pad for Power Series SSR heatsink, 10 pack
Z Series Solid State Relays
Z240D10-17
This Z Model, 240 VAC, 10 Amp, DC Control Solid State Relay (SSR) should be used as a replacement part only.
Z Model, 240 VAC, 10 Amp, DC Control Solid State Relay (SSR), Replacement Part Only
Z240D10-17
Nominal AC Line Voltage Nominal | 240 |
Current Rating (Amps) | 10 |
1 cycle Surge (Amps) Peak | 110 |
Nominal Signal Input Resistance (Ohms) | 1000 |
Signal Pick-up Voltage | 3VDC (32V allowed) |
Signal Drop-out Voltage | 1 VDC |
Peak Repetitive Voltage Maximum | 600 |
Maximum Output Voltage Drop | 1.6 volts |
Off-State Leakage (mA) Maximum** | 12 mA |
Operating Voltage Range (Volts AC) | 24-280 |
I2t Rating t=8.3 (ms) | 50 |
Isolation Voltage | 4,000 VRMS |
θjc* (°C/Watt) Dissipation (Watts/Amp) | 4 |
Agency Approvals | CE, CSA, RoHS, UKCA |
Notes: θjc* = Thermal resistance junction to base. Maximum junction temperature is 110°C. ** Operating Frequency: 25 to 65 Hz (operates at 400 Hz with 6 times the offstate leakage) |
Z240D10
The Z240D10 is a DC-controlled relay that switches 240 VAC at up to 10 A.
Z Model, 240 VAC, 10 Amp, DC Control Solid State Relay (SSR)
Z240D10
Nominal AC Line Voltage Nominal | 240 |
Current Rating (Amps) | 10 |
1 cycle Surge (Amps) Peak | 110 |
Nominal Signal Input Resistance (Ohms) | 1000 |
Signal Pick-up Voltage | 3VDC (32V allowed) |
Signal Drop-out Voltage | 1 VDC |
Peak Repetitive Voltage Maximum | 600 |
Maximum Output Voltage Drop | 1.6 volts |
Off-State Leakage (mA) Maximum** | 12 mA |
Operating Voltage Range (Volts AC) | 24-280 |
I2t Rating t=8.3 (ms) | 50 |
Isolation Voltage | 4,000 VRMS |
θjc* (°C/Watt) Dissipation (Watts/Amp) | 4 |
Agency Approvals | CE, CSA, RoHS, UKCA |
Notes: θjc* = Thermal resistance junction to base. Maximum junction temperature is 110°C. ** Operating Frequency: 25 to 65 Hz (operates at 400 Hz with 6 times the offstate leakage) |
Z120D10
The Z120D10 is a DC-controlled relay that switches 120 VAC at up to 10 A.
Z Model, 120 VAC, 10 Amp, DC Control Solid State Relay (SSR)
Z120D10
Nominal AC Line Voltage Nominal | 120 |
Current Rating (Amps) | 10 |
1 cycle Surge (Amps) Peak | 110 |
Nominal Signal Input Resistance (Ohms) | 1000 |
Signal Pick-up Voltage | 3VDC (32V allowed) |
Signal Drop-out Voltage | 1 VDC |
Peak Repetitive Voltage Maximum | 600 |
Maximum Output Voltage Drop | 1.6 volts |
Off-State Leakage (mA) Maximum** | 6 mA |
Operating Voltage Range (Volts AC) | 12-140 |
I2t Rating t=8.3 (ms) | 50 |
Isolation Voltage | 4,000 VRMS |
θjc* (°C/Watt) Dissipation (Watts/Amp) | 4 |
Agency Approvals | CE, CSA, RoHS, UKCA |
Notes: θjc* = Thermal resistance junction to base. Maximum junction temperature is 110°C. ** Operating Frequency: 25 to 65 Hz (operates at 400 Hz with 6 times the offstate leakage) |