G1 I/O family
The OAC5H output module is used for controlling or switching AC loads of 24-280 VAC and has a higher current rating than the OAC5.
Each module provides up to 4000 volts (transient) of optical isolation between the field devices and the control logic. This module is equivalent to a single pole, single throw, normally open contact (FORM A, SPST-NO, Make). All AC output modules feature zero voltage turn-on and zero current turn-off.
Typical uses and applications for AC output modules include switching the following loads:
– Relays
– Solenoids
– Motor starters
– Heaters
– Lamps or indicators